INDUSTRIAL

CABINET FREQUENCY CONVERTERS

Control cabinet ecoVert® solutions offer cost-effective, flexible and reliable automation solutions in power range from 75kW up to 2700 kW.

In addition to the frequency converter, the cabinet can be supplied with the following:

  • Protection class IP23 or IP54 / IP55
  • Cabinet enclosure Rittal VX25
  • Main isolating switch
  • Semiconductor fuses
  • Mains choke 
  • Mains filter class C3
  • Power connection terminals
  • Heat sink 

Along with other standard fittings such as heating, lighting, top-mounted cable glands etc., Breuer specialize in customized control cabinets. Examples include: metal fittings on the cabinet, colour, special dimensions, sea water resistance, metal frame with increased stiffness, hand rails according to DNV, cooling (reduction or air suction not on the bottom), PLC integration, AFE-power regeneration, protection class up to IP65, etc. A comprehensive protection and diagnostic concept ensures easy installation, and secure operation in rough environments.

Breuer can deliver components as well as total solutions containing switch gear, transformers, frequency converters and motors. Our project engineers will offer you support in component choosing, system design, project design, installation and commissioning. 

TECHNICAL DATA

Power range

75 kW to 2700 kW

Supply voltage

400 V to 480 V, 3 AC, -15 % to +10 %

600 V to 690 V, 3 AC, -15 % to +10 %

1140 V, 3 AC, -10 % to +10 %

3300 V , 3 AC

4160 V, 3 AC

Output voltage

0 to 0.98 Usupply

Output frequency

0.5 to 300 Hz

Operating frequency

50/60 Hz +/-5 %

Switching frequency

Rated operation at 4 kHz, from 160 kW 2 kHz, adjustable from 2 kHz to 16 kHz (from 160 kW to 8 kHz) at 400 V

Brake operation

Brake chopper or external Active Front End solution (power regeneration)

Protection class

IP20, IP54 as built-in unit or IP23, IP54 as control cabinet solution, higher class upon request

Overload current

Rated operation x 1,50

Auxiliary supply

AC 230 V

Ambient temperature

Rated operation at 40° C, with de-rating up to 50° C

Environmental conditions

IEC 60721-3-3 class 3C2 and 3S2

Cooling type

Forced air cooling or water cooling options

Motor control 

Asynchronous: Vector oriented control with / without encoder, 2- and 5-point U/f Synchronous: Vector oriented control with encoder 

Safety

STO dual-channel “safety stop“ 

and / or motor thermal protection of an ATEX certified motor in explosion-hazard environments

Communication

CANopen, Profibus DP, ProfiNet IO, EtherNet IP, etc.

EMC

According to IEC 61800-3, category C3 (C1, C2 with external filtering)

Certification

CE

DNV, ABS, BV, GL, LR as individual approval)

Software macros

Software modules (also optionally customized) for synchronization, Master/Slave, conveying and lifting equipment, anti-skid and anti-slip protection, traction, specialty modules for vertical drilling, pumping etc.

HMI and Start-up software

ecoWin® for easy installation, parameter setting, archiving and diagnostics